DGUV Regulation 3: Electrical Installations and Equipment

Accident prevention regulation of the German statutory accident insurance. Electrical installations and equipment must be inspected by a qualified electrician before first commissioning and at defined intervals. The implementing instructions give guideline values; the specific intervals follow from the risk assessment.

For operators
  • Set inspection intervals for fixed installations and portable equipment
  • Inspection by a qualified electrician or under their supervision
  • Block failed devices until they are repaired
  • Keep traceable inspection logs per device
With vi

vi reads inspection logs, even with hundreds of items under test, finds failed devices and creates a ticket for each one.

What applies when.

Adopted, in force, applicable: the milestones of DGUV V3 that matter for service and maintenance.

  1. 1 Apr 1979
    The accident prevention regulation enters into force (first adopted by a Berufsgenossenschaft). It replaces regulation VBG 4.
  2. 1 Jan 1997
    The version still published today, dated 1 January 1997, is created.
  3. 17 Jul 2026
    The DGUV announces that the revision of DGUV Regulations 3 and 4 has begun. The aim is simple rules that leave room for operating practice. No date for the new version is given.

Questions in detail.

Expand a question for the answer, the original wording of the rules and links to the official text.

Who does DGUV Regulation 3 apply to, and where does its binding force come from?

DGUV Regulation 3 is an accident prevention regulation. Under Book VII of the Social Code, the Berufsgenossenschaften and Unfallkassen may issue such regulations as statutory rules of their own. They bind the companies insured with them. The version that applies to you is the one from your accident insurance carrier, and the DGUV publishes the wording. DGUV Regulation 4 (formerly GUV-V A 3) is a parallel regulation with the same title that applies to other accident insurance carriers.

In scope, § 1 covers electrical installations and equipment as well as non-electrical work near them. The term equipment is broad. Under § 2(1), it includes objects for generating, distributing and consuming electrical energy, and equally objects of telecommunications and information technology. An installation is formed by connecting items of equipment.

The duty holder is the employer (Unternehmer). It remains responsible when it hands inspection or maintenance to an outside company. The regulation does not require a monitoring body as the BetrSichV does. It requires inspection by a qualified electrician. The BetrSichV also applies in parallel, because electrical installations and devices are work equipment and their inspection derives from the risk assessment. The DGUV announced in July 2026 that it is revising Regulations 3 and 4. Until a new version exists, the current text governs.

“This accident prevention regulation applies to electrical installations and equipment. […] This accident prevention regulation also applies to non-electrical work in the vicinity of electrical installations and equipment.”
§ 1(1) and (2)DGUV Regulation 3Original text ↗

Unofficial translation

“Electrical equipment within the meaning of this accident prevention regulation means all objects that serve, as a whole or in individual parts, the use of electrical energy […] or the transmission, distribution and processing of information […].”
§ 2(1)DGUV Regulation 3Original text ↗

Unofficial translation

Which inspections does the regulation require, and does it set fixed intervals?

Under § 5(1), electrical installations and equipment are to be inspected twice over their life: before first commissioning and, after a modification or repair, before restart, each time by a qualified electrician or under their direction and supervision, and after that at certain intervals. The inspection must follow the electrotechnical rules (§ 5(2)). The first inspection is not needed if the manufacturer or installer confirms that the installation meets the provisions of the regulation (§ 5(4)). According to the implementing instructions, usually only the installer can give that confirmation, because only the installer knows the conditions of use.

The text of the regulation contains no fixed numbers. It requires the intervals to be set so that defects that must be expected are found in time. The employer therefore sets the intervals itself and must be able to justify them. The implementing instructions offer tables of guideline values for this (see the next question). If you deviate from them, derive the deviation from the risk assessment and record it.

The inspection checks for proper condition. How to inspect is determined by the electrotechnical rules that § 5(2) refers to. The regulation itself names no measurement methods.

“The employer must ensure that the electrical installations and equipment are inspected for proper condition 1. before first commissioning and, after a modification or repair, before restart by a qualified electrician or under the direction and supervision of a qualified electrician and 2. at certain intervals. The intervals must be set so that defects that are to be expected are found in good time.”
§ 5(1)DGUV Regulation 3Original text ↗

Unofficial translation

“The inspection before first commissioning under paragraph 1 is not required if the manufacturer or installer confirms to the employer that the electrical installations and equipment are built in accordance with the provisions of this accident prevention regulation.”
§ 5(4)DGUV Regulation 3Original text ↗

Unofficial translation

Which inspection intervals are customary, and when may I extend or must I shorten them?

The implementing instructions to § 5 give guideline values for normal stress. Fixed electrical installations and equipment count as adequately inspected with an inspection by a qualified electrician every four years, and every year in locations, rooms and installations of a special kind (Table 1A). Users operate the test device of residual-current protective devices in stationary installations every six months and in non-stationary installations every working day. A qualified electrician or an instructed person checks the effectiveness of protective measures with residual-current devices in non-stationary installations every month. Portable equipment has a guideline value of six months, three months on construction sites (Table 1B). As maximum values, the table gives one year in manufacturing sites and workshops and two years in offices.

The failure rate decides. If the share of tested items with deviations is at most 2 percent, the interval can be regarded as sufficient and extended accordingly. If it is higher, shorten it. Where equipment is only lightly stressed, longer intervals are justified, according to the DGUV statement of 17 July 2026. Fixed installations can also be monitored continuously by qualified electricians if they are continuously maintained and monitored by measurement. This replaces the recurring inspection but does not apply to portable equipment.

The tables are guideline values, not mandatory intervals. Document the failure rate per operating area so that you can support an extension.

“The following tables can be used to set inspection intervals if the electrical installations and equipment are exposed to normal stresses from ambient temperature, dust, humidity or the like.”
Implementing instruction on § 5(1) No. 2DGUV Regulation 3 DA (implementing instructions)Original text ↗

Unofficial translation

“If the failure rate is at most 2 %, the inspection interval can be regarded as sufficient.”
Implementing instruction on § 5(1) No. 2DGUV Regulation 3 DA (implementing instructions)Original text ↗

Unofficial translation

Who may inspect and maintain electrical installations and devices?

The regulation distinguishes two qualification levels. Under § 2(3), a qualified electrician is someone who, based on technical training, knowledge, experience and knowledge of the relevant provisions, can assess the work assigned to them and recognize possible hazards. The qualification relates to the work assigned, not to a title.

Under § 3(1), the qualified electrician carries out the installing, modifying and maintaining, or directs and supervises it. That applies to service technicians who work on an installation as well. The same goes for inspections: § 5(1) requires a qualified electrician or their direction and supervision. The implementing instructions allow instructed persons to inspect as well if suitable measuring and testing devices are available and a qualified electrician directs and supervises. Responsibility for proper execution stays with the qualified electrician. For portable equipment, an instructed person may take on that responsibility if they use suitable measuring devices.

Users perform the test of residual-current protective devices with the test button themselves. Ask inspection service providers to prove the qualifications of the people they send, and record who inspected under whose supervision.

“A qualified electrician within the meaning of this accident prevention regulation is someone who, based on technical training, knowledge and experience and knowledge of the relevant provisions, can assess the work assigned to them and recognize possible hazards.”
§ 2(3)DGUV Regulation 3Original text ↗

Unofficial translation

“The employer must ensure that electrical installations and equipment are installed, modified and maintained in accordance with the electrotechnical rules only by a qualified electrician or under the direction and supervision of a qualified electrician.”
§ 3(1)DGUV Regulation 3Original text ↗

Unofficial translation

“If suitable measuring and testing devices are available for the measuring and testing tasks, electrotechnically instructed persons may also inspect under the direction and supervision of a qualified electrician.”
Implementing instruction on § 5(1) No. 2DGUV Regulation 3 DA (implementing instructions)Original text ↗

Unofficial translation

What applies when a device fails the inspection or a defect appears?

If a defect has been found in an electrical installation or piece of equipment, meaning it does not or no longer meets the electrotechnical rules, the employer must ensure that the defect is corrected without delay (§ 3(2)). If there is an urgent danger until then, the device or installation may not be used in its defective condition. A device that failed is therefore locked out, clearly marked and taken out of circulation until it has been repaired and inspected again.

After a repair, § 5(1) requires another inspection before restart. A repair without a following inspection is not enough. That also applies to parts a service technician has replaced.

The regulation does not prescribe an inspection sticker, but it is common practice, as the DGUV itself describes. If you use stickers, apply them only once the defects found have been corrected. Otherwise, the sticker shows a device as inspected that is not yet in order.

When you inspect many items, it is easy to lose track of which devices failed and what follows. vi reads such inspection logs, finds the failed devices and creates a ticket for each one.

“If a defect has been found in an electrical installation or an electrical item of equipment, that is, if they do not or no longer comply with the electrotechnical rules, the employer must ensure that the defect is corrected without delay and, if there is an urgent danger until then, must ensure that the electrical installation or the electrical equipment is not used in its defective condition.”
§ 3(2)DGUV Regulation 3Original text ↗

Unofficial translation

“The electrotechnical rules relating to the inspection must be observed.”
§ 5(2)DGUV Regulation 3Original text ↗

Unofficial translation

Which records are required, and what happens in case of violations?

The regulation requires an inspection logbook with certain entries only on request of the Berufsgenossenschaft (§ 5(3)). The text names no format and no retention period. In practice, the log holds, per installation or device, the inspection date, the inspector, the rules applied, the measured values, the result and the next due date. If you want to extend intervals, you also need the failure rate per operating area. Under the BetrSichV, the documentation of the risk assessment and the inspection result come on top.

Violations of § 3, § 5(1) to (3), § 6 and § 7 are administrative offenses under § 209 of Book VII of the Social Code, according to § 9 of the regulation. The fine can be up to 10,000 euros (§ 209(3) SGB VII). The supervisory officers of the accident insurance carriers can order in individual cases which measures the employer must take to meet its duties. They may enter business premises, inspect documents and examine work equipment (§ 19 SGB VII).

The DGUV names the background: every year, companies report about 2,500 occupational accidents involving electric current, some of them fatal. Complete records help during supervision and, if an accident happens, in clarifying responsibility.

“At the request of the Berufsgenossenschaft, an inspection logbook with certain entries must be kept.”
§ 5(3)DGUV Regulation 3Original text ↗

Unofficial translation

“The administrative offense can be punished with a fine of up to ten thousand euros in the cases of paragraph 1 numbers 1 to 3a, […].”
§ 209(3)Book VII of the Social Code (SGB VII)Original text ↗